model
TS510W x H x D (㎜)
145 x 145 x 33.5power supply voltage
100 – 240 V ac voltage variation rate ±10%Power frequency
50-60 kgConsume electricity
30 VA maxWithstand voltage
– Input and output terminals: Minimum 1500 V ac for 1 minute– Input terminals and FG terminals: Minimum 1500 V ac for 1 minute.
– Output terminals and FG terminals: Minimum 1500 V ac for 1 minuteInput types
– 11 types of thermocouples (K, J, E, T, R, B, S, L, N, U, Wre 5-26) ±0.15% of FS ±1 digit
– Two types of resistance temperature detectors (RTDs) (Pt-100, KPt-100) ±0.1% of FS ±1 Digit,
– Current and voltage ratings (4 values : -10 – 20 mV, 0 – 100 mV, 1 – 5 V, 0 – 30 V) ±0.1% of FS ±1 DigitSampling period
250 msContact input (DO)
relay contacts
Up to 32 points
A contact
30 V dc max. 3 A, 250 V ac 3 AB contact
NO: 30 V dc max 5 A, 250 V ac 5 AControl input
SSR Output
ON: 18 V DC pulse voltage (load resistance above 800 Ω)SCR output
4 – 20 mA dc (load resistance below 600 Ω)Transmission output
Current output
4 – 20 mA dcLoad impedance
Load resistance below 600 ΩOutput types
Laboratory PV, Laboratory SV, High-temperature greenhouse PV, Low-temperature greenhouse PVUpdate cycle
250 ms
Function
enter
Input correction
EUS (0 ~ 100%)Input filtering
0 ~ 120 secondsControl output
Selectable output (SSR) or current output (4 – 20 mA dc)Control Action
Test mode
Maximum of 100, with 10 test types selected for each mode.PID group
Four groups each for high-temperature greenhouse and low-temperature greenhouse, with PID deviation.Automatic calculation
Automatic calculation based on target set valueBili belt
0.00 ~ 100.00% (ON/OFF control at 0.00%)Integral time / Differential time
0.0 ~ 3000 seconds (OFF state when set to 0 seconds)ON/OFF control
Set the ratio band to 0 (PB) and set it to 0.0.Forward/ Reverse
Based on the positive/reverse action of the control inputForward/ Reverse
ARW zone setting (50 ~ 1,000% of the belt width)AT GAIN
0.0 ~ 10.0Alarm settings
Set alarm
System alarm at 8 o’clockAlarm types
Absolute upper and lower limits, deviation upper and lower limits, within and outside the range (alarm direction, maintain).Absolute alarm setting range
EU (0 ~ 100%)Image specifications
TFT color LCD (115.2 x 86.4 mm)resolution
640 x 480 pixelsBacklight
LED backlightBacklight lifespan
Approximately 40,000 hTouch type
Resistive touchscreen (4-wire)Language used
Korean/English/Simplified ChineseStorage function
Memory (non-volatile memory: 80 MB), external storage (SD card (4 GB)), storage cycle (1 ~ 360 seconds)Memory information
Stored program information and settings, storage recovery, temperature and humidity settings, and indicator values.Operating environment temperature and humidity
0 ~ 50 ℃, 20 ~ 90 % RH (but no condensation)weight
Approximately 1.32 kg